Skip to content

CVE-2018-11451 A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware vari...

HighCVSS 7.5 EPSS 2.4%
Published
Updated
Exploit status
No public exploit known

Description

A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.80), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.58). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the affected products. A manual restart is required to recover the EN100 module functionality of the affected devices. Successful exploitation requires an attacker with network access to send multiple packets to the affected products or modules. As a precondition the IEC 61850-MMS communication needs to be activated on the affected products or modules. No user interaction or privileges are required to exploit the vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Upgrade path

15 packages: 3 fixed, 5 with no fix yet.

PackageAffectedFixed inStatus
Siemens cp200 firmware All versions No fix listed No fix yet
Siemens dnp3 tcp firmware All versions No fix listed No fix yet
Siemens iec104 firmware All versions No fix listed No fix yet
Siemens modbus tcp firmware All versions No fix listed No fix yet
Siemens profinet io firmware All versions No fix listed No fix yet
Siemens cp100 firmware < 7.80 7.80 Fixed
Siemens cp300 firmware < 7.80 7.80 Fixed
Siemens iec 61850 firmware < 4.33 4.33 Fixed
Siemens Firmware variant DNP3 TCP for EN100 Ethernet module = All versions No fix listed Versions listed
Siemens Firmware variant IEC 61850 for EN100 Ethernet module = All versions < V4.33 No fix listed Versions listed
Siemens Firmware variant IEC104 for EN100 Ethernet module = All versions < V1.22 No fix listed Versions listed
Siemens Firmware variant MODBUS TCP for EN100 Ethernet module = All versions No fix listed Versions listed
Siemens Firmware variant Profinet IO for EN100 Ethernet module = All versions No fix listed Versions listed
Siemens SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules = All versions < V7.58 No fix listed Versions listed
Siemens SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules = All versions < V7.80 No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
Siemens dnp3 tcp firmware All versions No fix listed
Siemens iec 61850 firmware < 4.33 4.33
Siemens iec104 firmware All versions No fix listed
Siemens modbus tcp firmware All versions No fix listed
Siemens profinet io firmware All versions No fix listed
Siemens cp100 firmware < 7.80 7.80
Siemens cp200 firmware All versions No fix listed
Siemens cp300 firmware < 7.80 7.80
Siemens Firmware variant IEC 61850 for EN100 Ethernet module = All versions < V4.33 No fix listed
Siemens Firmware variant Profinet IO for EN100 Ethernet module = All versions No fix listed
Siemens Firmware variant MODBUS TCP for EN100 Ethernet module = All versions No fix listed
Siemens Firmware variant DNP3 TCP for EN100 Ethernet module = All versions No fix listed
Siemens Firmware variant IEC104 for EN100 Ethernet module = All versions < V1.22 No fix listed
Siemens SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules = All versions < V7.80 No fix listed
Siemens SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules = All versions < V7.58 No fix listed

References