CVE-2018-4838 A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (All versions < V1.04), EN100 Ethernet module PROFINET IO vari...
- Published
- Updated
- Exploit status
- No public exploit known
Description
A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (All versions < V1.04), EN100 Ethernet module PROFINET IO variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions < V1.22). The web interface (TCP/80) of affected devices allows an unauthenticated user to upgrade or downgrade the firmware of the device, including to older versions with known vulnerabilities.
Upgrade path
10 packages: 1 fixed, 4 with no fix yet.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| Siemens en100 ethernet module dnp3 firmware | All versions | No fix listed | No fix yet |
| Siemens en100 ethernet module iec 104 firmware | All versions | No fix listed | No fix yet |
| Siemens en100 ethernet module modbus tcp firmware | All versions | No fix listed | No fix yet |
| Siemens en100 ethernet module profinet io firmware | All versions | No fix listed | No fix yet |
| Siemens en100 ethernet module iec 61850 firmware | < 4.30 | 4.30 | Fixed |
| Siemens EN100 Ethernet module DNP3 variant | = All versions < V1.04 | No fix listed | Versions listed |
| Siemens EN100 Ethernet module IEC 104 variant | = All versions < V1.22 | No fix listed | Versions listed |
| Siemens EN100 Ethernet module IEC 61850 variant | = All versions < V4.30 | No fix listed | Versions listed |
| Siemens EN100 Ethernet module Modbus TCP variant | = All versions | No fix listed | Versions listed |
| Siemens EN100 Ethernet module PROFINET IO variant | = All versions | No fix listed | Versions listed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Siemens en100 ethernet module iec 104 firmware | All versions | No fix listed |
| Siemens en100 ethernet module dnp3 firmware | All versions | No fix listed |
| Siemens en100 ethernet module modbus tcp firmware | All versions | No fix listed |
| Siemens en100 ethernet module profinet io firmware | All versions | No fix listed |
| Siemens en100 ethernet module iec 61850 firmware | < 4.30 | 4.30 |
| Siemens EN100 Ethernet module IEC 61850 variant | = All versions < V4.30 | No fix listed |
| Siemens EN100 Ethernet module DNP3 variant | = All versions < V1.04 | No fix listed |
| Siemens EN100 Ethernet module PROFINET IO variant | = All versions | No fix listed |
| Siemens EN100 Ethernet module Modbus TCP variant | = All versions | No fix listed |
| Siemens EN100 Ethernet module IEC 104 variant | = All versions < V1.22 | No fix listed |
References
- cert-portal.siemens.com patch vendor-advisory
- 103379 vdb-entry
- ics-cert.us-cert.gov third-party-advisory us-government-resource