Skip to content

CVE-2018-4858 A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All ve...

HighCVSS 7.8 EPSS 1.8%
Published
Updated
Exploit status
No public exploit known
Technology
Windows

Description

A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.

Upgrade path

7 packages: 4 fixed, 2 with no fix yet.

PackageAffectedFixed inStatus
Siemens digsi 4 firmware All versions No fix listed No fix yet
Siemens sicam scc firmware All versions No fix listed No fix yet
Siemens digsi 5 firmware < 7.80 7.80 Fixed
Siemens ec 61850 system configurator firmware < 5.80 5.80 Fixed
Siemens sicam paspqs < 8.11 8.11 Fixed
Siemens sicam pq analyzer firmware < 3.11 3.11 Fixed
Siemens IEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, SICAM SCC = DIGSI 4 : All versions < V4.93; = DIGSI 5 (affected as IEC 61850 system configurator is incorporated) : All versions < V7.80; = IEC 61850 system configurator : All versions < V5.80; = SICAM PAS/PQS : All versions < V8.11 +2 more No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
Siemens ec 61850 system configurator firmware < 5.80 5.80
Siemens sicam pq analyzer firmware < 3.11 3.11
Siemens sicam scc firmware All versions No fix listed
Siemens digsi 4 firmware All versions No fix listed
Siemens digsi 5 firmware < 7.80 7.80
Siemens sicam paspqs < 8.11 8.11
Siemens IEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, SICAM SCC = IEC 61850 system configurator : All versions < V5.80 No fix listed
Siemens IEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, SICAM SCC = DIGSI 5 (affected as IEC 61850 system configurator is incorporated) : All versions < V7.80 No fix listed
Siemens IEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, SICAM SCC = DIGSI 4 : All versions < V4.93 No fix listed
Siemens IEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, SICAM SCC = SICAM PAS/PQS : All versions < V8.11 No fix listed
Siemens IEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, SICAM SCC = SICAM PQ Analyzer : All versions < V3.11 No fix listed
Siemens IEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, SICAM SCC = SICAM SCC : All versions < V9.02 HF3 No fix listed

References