CVE-2018-7245 An improper authorization vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the...
CriticalCVSS 9.1
EPSS 1.2%
- Published
- Updated
- Exploit status
- No public exploit known
Description
An improper authorization vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to change UPS control and shutdown parameters or other critical settings without authorization.
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| schneider-electric 66074 mge network management card transverse | All versions | No fix listed |
| Schneider Electric SE 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS | = MGE Network Management Card Transverse, part number: SF66074. All card versions affected, when installed in following products: MGE Galaxy 5000, MGE Galaxy 6000, MGE Galaxy 9000, MGE EPS 7000 | No fix listed |