CVE-2020-10920 This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit th...

CriticalCVSS 9.8 EPSS 4.9%
Published
Updated
Exploit status
No public exploit known

Description

This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the control service, which listens on TCP port 9999 by default. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to execute code in the context of the device. Was ZDI-CAN-10493.

Upgrade path

2 packages: 0 fixed.

PackageAffectedFixed inStatus
AutomationDirect c-more hmi ea9 firmware = 6.52 No fix listed Versions listed
C-MORE HMI EA9 = Firmware version 6.52 No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
AutomationDirect c-more hmi ea9 firmware = 6.52 No fix listed
C-MORE HMI EA9 = Firmware version 6.52 No fix listed

References