Skip to content

CVE-2020-24685 AC500 V2 unauthenticated crafter packet vulnerability

HighCVSS 8.6 EPSS 1.6%
Published
Updated
Exploit status
No public exploit known

Description

An unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC. After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application. This issue affects: ABB AC500 V2 products with onboard Ethernet version 2.8.4 and prior versions.

Upgrade path

2 packages: 1 fixed.

PackageAffectedFixed inStatus
ABB ac500 cpu firmware < 2.8.5 2.8.5 Fixed
ABB AC500 V2 products with onboard Ethernet = version 2.8.4 and prior versions No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
ABB ac500 cpu firmware < 2.8.5 2.8.5
ABB AC500 V2 products with onboard Ethernet = version 2.8.4 and prior versions No fix listed

References