CVE-2020-25178 Rockwell Automation ISaGRAF5 Runtime Cleartext Transmission of Sensitive Information
HighCVSS 8.8
EPSS 1.7%
- Published
- Updated
- Exploit status
- No public exploit known
- CISA SSVC
- No known exploitation · automatable: no · technical impact: total
Description
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
Upgrade path
18 packages: 10 fixed, 5 with no fix yet.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| rockwellautomation micro810 firmware | All versions | No fix listed | No fix yet |
| rockwellautomation micro820 firmware | All versions | No fix listed | No fix yet |
| rockwellautomation micro830 firmware | All versions | No fix listed | No fix yet |
| rockwellautomation micro850 firmware | All versions | No fix listed | No fix yet |
| rockwellautomation micro870 firmware | All versions | No fix listed | No fix yet |
| rockwellautomation aadvance controller | <= 1.40 | after 1.40 | Fixed |
| rockwellautomation isagraf free runtime | <= 6.6.8 | after 6.6.8 | Fixed |
| rockwellautomation isagraf runtime | >= 5.0, < 6.0 | 6.0 | Fixed |
| schneider-electric easergy c5 firmware | < 1.1.0 | 1.1.0 | Fixed |
| schneider-electric easergy t300 firmware | <= 2.7.1 | after 2.7.1 | Fixed |
| schneider-electric micom c264 firmware | < d6.1 | d6.1 | Fixed |
| schneider-electric saitel dp firmware | <= 11.06.21 | after 11.06.21 | Fixed |
| schneider-electric saitel dr firmware | <= 11.06.12 | after 11.06.12 | Fixed |
| schneider-electric scd2200 firmware | <= 10024 | after 10024 | Fixed |
| xylem multismart firmware | < 3.2.0 | 3.2.0 | Fixed |
| Rockwell Automation ISaGRAF Runtime | = 4.x; = 5.x | No fix listed | Versions listed |
| schneider-electric epas gtw firmware | = 6.4 | No fix listed | Versions listed |
| schneider-electric pacis gtw firmware | = 5.1; = 5.2; = 6.1; = 6.3 | No fix listed | Versions listed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| schneider-electric easergy t300 firmware | <= 2.7.1 | No fix listed |
| schneider-electric easergy c5 firmware | < 1.1.0 | 1.1.0 |
| schneider-electric micom c264 firmware | < d6.1 | d6.1 |
| schneider-electric pacis gtw firmware | = 5.1 | No fix listed |
| schneider-electric pacis gtw firmware | = 5.2 | No fix listed |
| schneider-electric pacis gtw firmware | = 6.1 | No fix listed |
| schneider-electric pacis gtw firmware | = 6.3 | No fix listed |
| schneider-electric saitel dp firmware | <= 11.06.21 | No fix listed |
| schneider-electric epas gtw firmware | = 6.4 | No fix listed |
| schneider-electric saitel dr firmware | <= 11.06.12 | No fix listed |
| schneider-electric scd2200 firmware | <= 10024 | No fix listed |
| rockwellautomation aadvance controller | <= 1.40 | No fix listed |
| rockwellautomation isagraf free runtime | <= 6.6.8 | No fix listed |
| rockwellautomation isagraf runtime | >= 5.0, < 6.0 | 6.0 |
| rockwellautomation micro810 firmware | All versions | No fix listed |
| rockwellautomation micro820 firmware | All versions | No fix listed |
| rockwellautomation micro830 firmware | All versions | No fix listed |
| rockwellautomation micro850 firmware | All versions | No fix listed |
| rockwellautomation micro870 firmware | All versions | No fix listed |
| xylem multismart firmware | < 3.2.0 | 3.2.0 |
| Rockwell Automation ISaGRAF Runtime | = 4.x | No fix listed |
| Rockwell Automation ISaGRAF Runtime | = 5.x | No fix listed |
References
- download.schneider-electric.com vendor-advisory
- rockwellautomation.custhelp.com permissions-required
- www.cisa.gov third-party-advisory us-government-resource
- www.xylem.com vendor-advisory