Skip to content

CVE-2020-27736 A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5....

MediumCVSS 6.5 EPSS 4.0%
Published
Updated
Exploit status
No public exploit known

Description

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.

Upgrade path

12 packages: 3 fixed, 2 with no fix yet.

PackageAffectedFixed inStatus
Siemens nucleus net = All versions; All versions No fix listed No fix yet
Siemens Nucleus Source Code = Versions including affected DNS modules; All versions No fix listed No fix yet
Siemens nucleus readystart v3 < 2017.02.3; = All versions < V2017.02.3 2017.02.3 Fixed
Siemens nucleus readystart v4 < 4.1.0; = All versions < V4.1.0 4.1.0 Fixed
Siemens simotics connect 400 firmware < 0.5.0.0 0.5.0.0 Fixed
Siemens APOGEE PXC Compact (BACnet) = All versions < V3.5.5 No fix listed Versions listed
Siemens APOGEE PXC Compact (P2 Ethernet) = All versions < V2.8.20 No fix listed Versions listed
Siemens APOGEE PXC Modular (BACnet) = All versions < V3.5.5 No fix listed Versions listed
Siemens APOGEE PXC Modular (P2 Ethernet) = All versions < V2.8.20 No fix listed Versions listed
Siemens SIMOTICS CONNECT 400 = All versions < V0.5.0.0 No fix listed Versions listed
Siemens TALON TC Compact (BACnet) = All versions < V3.5.5 No fix listed Versions listed
Siemens TALON TC Modular (BACnet) = All versions < V3.5.5 No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
Siemens nucleus net All versions No fix listed
Siemens nucleus readystart v3 < 2017.02.3 2017.02.3
Siemens nucleus readystart v4 < 4.1.0 4.1.0
Siemens Nucleus Source Code All versions No fix listed
Siemens simotics connect 400 firmware < 0.5.0.0 0.5.0.0
Siemens APOGEE PXC Compact (BACnet) = All versions < V3.5.5 No fix listed
Siemens APOGEE PXC Compact (P2 Ethernet) = All versions < V2.8.20 No fix listed
Siemens APOGEE PXC Modular (BACnet) = All versions < V3.5.5 No fix listed
Siemens APOGEE PXC Modular (P2 Ethernet) = All versions < V2.8.20 No fix listed
Siemens nucleus net = All versions No fix listed
Siemens nucleus readystart v3 = All versions < V2017.02.3 No fix listed
Siemens nucleus readystart v4 = All versions < V4.1.0 No fix listed
Siemens Nucleus Source Code = Versions including affected DNS modules No fix listed
Siemens SIMOTICS CONNECT 400 = All versions < V0.5.0.0 No fix listed
Siemens TALON TC Compact (BACnet) = All versions < V3.5.5 No fix listed
Siemens TALON TC Modular (BACnet) = All versions < V3.5.5 No fix listed

References