CVE-2020-27737 A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5....
- Published
- Updated
- Exploit status
- No public exploit known
Description
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS response parsing functionality does not properly validate various length and counts of the records. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the memory past the allocated structure.
Upgrade path
12 packages: 3 fixed, 2 with no fix yet.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| Siemens nucleus net | = All versions; All versions | No fix listed | No fix yet |
| Siemens Nucleus Source Code | = Versions including affected DNS modules; All versions | No fix listed | No fix yet |
| Siemens nucleus readystart v3 | < 2017.02.3; = All versions < V2017.02.3 | 2017.02.3 | Fixed |
| Siemens nucleus readystart v4 | < 4.1.0; = All versions < V4.1.0 | 4.1.0 | Fixed |
| Siemens simotics connect 400 firmware | < 0.5.0.0 | 0.5.0.0 | Fixed |
| Siemens APOGEE PXC Compact (BACnet) | = All versions < V3.5.5 | No fix listed | Versions listed |
| Siemens APOGEE PXC Compact (P2 Ethernet) | = All versions < V2.8.20 | No fix listed | Versions listed |
| Siemens APOGEE PXC Modular (BACnet) | = All versions < V3.5.5 | No fix listed | Versions listed |
| Siemens APOGEE PXC Modular (P2 Ethernet) | = All versions < V2.8.20 | No fix listed | Versions listed |
| Siemens SIMOTICS CONNECT 400 | = All versions < V0.5.0.0 | No fix listed | Versions listed |
| Siemens TALON TC Compact (BACnet) | = All versions < V3.5.5 | No fix listed | Versions listed |
| Siemens TALON TC Modular (BACnet) | = All versions < V3.5.5 | No fix listed | Versions listed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Siemens simotics connect 400 firmware | < 0.5.0.0 | 0.5.0.0 |
| Siemens nucleus net | All versions | No fix listed |
| Siemens nucleus readystart v3 | < 2017.02.3 | 2017.02.3 |
| Siemens nucleus readystart v4 | < 4.1.0 | 4.1.0 |
| Siemens Nucleus Source Code | All versions | No fix listed |
| Siemens APOGEE PXC Compact (BACnet) | = All versions < V3.5.5 | No fix listed |
| Siemens APOGEE PXC Compact (P2 Ethernet) | = All versions < V2.8.20 | No fix listed |
| Siemens APOGEE PXC Modular (BACnet) | = All versions < V3.5.5 | No fix listed |
| Siemens APOGEE PXC Modular (P2 Ethernet) | = All versions < V2.8.20 | No fix listed |
| Siemens nucleus net | = All versions | No fix listed |
| Siemens nucleus readystart v3 | = All versions < V2017.02.3 | No fix listed |
| Siemens nucleus readystart v4 | = All versions < V4.1.0 | No fix listed |
| Siemens Nucleus Source Code | = Versions including affected DNS modules | No fix listed |
| Siemens SIMOTICS CONNECT 400 | = All versions < V0.5.0.0 | No fix listed |
| Siemens TALON TC Compact (BACnet) | = All versions < V3.5.5 | No fix listed |
| Siemens TALON TC Modular (BACnet) | = All versions < V3.5.5 | No fix listed |
References
- cert-portal.siemens.com
- cert-portal.siemens.com patch vendor-advisory