CVE-2021-31345 A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versions). The total leng...
CriticalCVSS 9.1
EPSS 1.6%
- Published
- Updated
- Exploit status
- No public exploit known
Description
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versions). The total length of an UDP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on a user-defined applications that runs on top of the UDP protocol. (FSMD-2021-0006)
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Siemens capital vstar | All versions | No fix listed |
| Siemens nucleus net | All versions | No fix listed |
| Siemens nucleus readystart v3 | < 2014.12 | 2014.12 |
| Siemens Nucleus Source Code | All versions | No fix listed |
| Siemens apogee modular building controller firmware | All versions | No fix listed |
| Siemens apogee modular equiment controller firmware | All versions | No fix listed |
| Siemens apogee pxc compact firmware | All versions | No fix listed |
| Siemens apogee pxc modular firmware | All versions | No fix listed |
| Siemens talon tc compact firmware | All versions | No fix listed |
| Siemens talon tc modular firmware | All versions | No fix listed |
| Siemens Capital Embedded AR Classic 431-422 | All versions | No fix listed |
| Siemens Capital Embedded AR Classic R20-11 | < V2303 | V2303 |
| Siemens pluscontrol 1st gen | = All versions | No fix listed |