CVE-2021-41545 A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All ve...
HighCVSS 7.5
EPSS 0.93%
- Published
- Updated
- Exploit status
- No public exploit known
Description
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.
Upgrade path
8 packages: 4 fixed.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| Siemens desigo dxr2 firmware | < 01.21.142.5-22 | 01.21.142.5-22 | Fixed |
| Siemens desigo pxc3 firmware | < 01.21.142.4-18 | 01.21.142.4-18 | Fixed |
| Siemens desigo pxc4 firmware | < 02.20.142.10-10884 | 02.20.142.10-10884 | Fixed |
| Siemens desigo pxc5 firmware | < 02.20.142.10-10884 | 02.20.142.10-10884 | Fixed |
| Siemens Desigo DXR2 | = All versions < V01.21.142.5-22 | No fix listed | Versions listed |
| Siemens Desigo PXC3 | = All versions < V01.21.142.4-18 | No fix listed | Versions listed |
| Siemens Desigo PXC4 | = All versions < V02.20.142.10-10884 | No fix listed | Versions listed |
| Siemens Desigo PXC5 | = All versions < V02.20.142.10-10884 | No fix listed | Versions listed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Siemens desigo dxr2 firmware | < 01.21.142.5-22 | 01.21.142.5-22 |
| Siemens desigo pxc3 firmware | < 01.21.142.4-18 | 01.21.142.4-18 |
| Siemens desigo pxc4 firmware | < 02.20.142.10-10884 | 02.20.142.10-10884 |
| Siemens desigo pxc5 firmware | < 02.20.142.10-10884 | 02.20.142.10-10884 |
| Siemens Desigo DXR2 | = All versions < V01.21.142.5-22 | No fix listed |
| Siemens Desigo PXC3 | = All versions < V01.21.142.4-18 | No fix listed |
| Siemens Desigo PXC4 | = All versions < V02.20.142.10-10884 | No fix listed |
| Siemens Desigo PXC5 | = All versions < V02.20.142.10-10884 | No fix listed |
References
- cert-portal.siemens.com vendor-advisory