CVE-2022-2502 A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with...

HighCVSS 7.5 EPSS 0.83%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: yes · technical impact: partial

Description

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.

Upgrade path

2 packages: 0 fixed.

PackageAffectedFixed inStatus
Hitachi Energy RTU500 series = RTU500 series CMU Firmware version 13.3.1; = RTU500 series CMU Firmware version 13.3.2 No fix listed Versions listed
hitachienergy rtu500 firmware = 13.3.1; = 13.3.2; = 13.3.3; = 13.4.1 No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
Hitachi Energy RTU500 series = RTU500 series CMU Firmware version 13.3.1 No fix listed
Hitachi Energy RTU500 series = RTU500 series CMU Firmware version 13.3.2 No fix listed
hitachienergy rtu500 firmware = 13.3.1 No fix listed
hitachienergy rtu500 firmware = 13.3.2 No fix listed
hitachienergy rtu500 firmware = 13.3.3 No fix listed
hitachienergy rtu500 firmware = 13.4.1 No fix listed