CVE-2022-28613 Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series

HighCVSS 7.5 EPSS 0.99%
Published
Updated
Exploit status
No public exploit known

Description

A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

Upgrade path

3 packages: 2 fixed, 1 with no fix yet.

PackageAffectedFixed inStatus
Hitachi Energy RTU500 series CMU firmware All versions No fix listed No fix yet
ABB rtu500 firmware >= 12.2.1.0, < 12.2.12.0 12.2.12.0 Fixed
hitachienergy rtu500 firmware >= 12.0.1.0, < 12.0.14.0; >= 12.4.1.0, < 12.4.12.0; >= 12.6.1.0, < 12.6.8.0; >= 12.7.1.0, < 12.7.4.0 +1 more 12.0.14.0, 12.4.12.0, 12.6.8.0, 12.7.4.0, 13.2.5.0 Fixed

Affected products

ProductAffected versionsFixed in
Hitachi Energy RTU500 series CMU firmware All versions No fix listed
ABB rtu500 firmware >= 12.2.1.0, < 12.2.12.0 12.2.12.0
hitachienergy rtu500 firmware >= 12.0.1.0, < 12.0.14.0 12.0.14.0
hitachienergy rtu500 firmware >= 12.4.1.0, < 12.4.12.0 12.4.12.0
hitachienergy rtu500 firmware >= 12.6.1.0, < 12.6.8.0 12.6.8.0
hitachienergy rtu500 firmware >= 12.7.1.0, < 12.7.4.0 12.7.4.0
hitachienergy rtu500 firmware >= 13.2.1.0, < 13.2.5.0 13.2.5.0