CVE-2022-28613 Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series
HighCVSS 7.5
EPSS 0.99%
- Published
- Updated
- Exploit status
- No public exploit known
Description
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
Upgrade path
3 packages: 2 fixed, 1 with no fix yet.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| Hitachi Energy RTU500 series CMU firmware | All versions | No fix listed | No fix yet |
| ABB rtu500 firmware | >= 12.2.1.0, < 12.2.12.0 | 12.2.12.0 | Fixed |
| hitachienergy rtu500 firmware | >= 12.0.1.0, < 12.0.14.0; >= 12.4.1.0, < 12.4.12.0; >= 12.6.1.0, < 12.6.8.0; >= 12.7.1.0, < 12.7.4.0 +1 more | 12.0.14.0, 12.4.12.0, 12.6.8.0, 12.7.4.0, 13.2.5.0 | Fixed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Hitachi Energy RTU500 series CMU firmware | All versions | No fix listed |
| ABB rtu500 firmware | >= 12.2.1.0, < 12.2.12.0 | 12.2.12.0 |
| hitachienergy rtu500 firmware | >= 12.0.1.0, < 12.0.14.0 | 12.0.14.0 |
| hitachienergy rtu500 firmware | >= 12.4.1.0, < 12.4.12.0 | 12.4.12.0 |
| hitachienergy rtu500 firmware | >= 12.6.1.0, < 12.6.8.0 | 12.6.8.0 |
| hitachienergy rtu500 firmware | >= 12.7.1.0, < 12.7.4.0 | 12.7.4.0 |
| hitachienergy rtu500 firmware | >= 13.2.1.0, < 13.2.5.0 | 13.2.5.0 |
References
- publisher.hitachienergy.com vendor-advisory
- search.abb.com