CVE-2022-29492 A vulnerability exists in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This...

HighCVSS 7.5 EPSS 0.89%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: yes · technical impact: partial

Description

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:::::::*

Upgrade path

3 packages: 2 fixed.

PackageAffectedFixed inStatus
Hitachi Energy MicroSCADA Pro SYS600 <= 9.2 FP2 Hotfix 4 after 9.2 FP2 Hotfix 4 Fixed
hitachienergy microscada x sys600 >= 9.0, < 10.4 10.4 Fixed
Hitachi Energy MicroSCADA X SYS600 = 10; = 10.1; = 10.1.1; = 10.2 +3 more No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
Hitachi Energy MicroSCADA X SYS600 = 10 No fix listed
Hitachi Energy MicroSCADA X SYS600 = 10.1 No fix listed
Hitachi Energy MicroSCADA X SYS600 = 10.1.1 No fix listed
Hitachi Energy MicroSCADA X SYS600 = 10.2 No fix listed
Hitachi Energy MicroSCADA X SYS600 = 10.2.1 No fix listed
Hitachi Energy MicroSCADA X SYS600 = 10.3 No fix listed
Hitachi Energy MicroSCADA X SYS600 = 10.3.1 No fix listed
Hitachi Energy MicroSCADA Pro SYS600 <= 9.2 FP2 Hotfix 4 No fix listed
hitachienergy microscada x sys600 >= 9.0, < 10.4 10.4