Skip to content

CVE-2022-33174 Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an H...

HighCVSS 7.5 EPSS 14.1% Scanner template
Published
Updated
Exploit status
No public exploit known

Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Upgrade path

7 packages: 7 fixed.

PackageAffectedFixed inStatus
powertekpdus basic pdu firmware < 3.30.30 3.30.30 Fixed
powertekpdus piml pdu firmware < 3.30.30 3.30.30 Fixed
powertekpdus pm pdu firmware < 3.30.30 3.30.30 Fixed
powertekpdus smart pim firmware < 3.30.30 3.30.30 Fixed
powertekpdus smart pom firmware < 3.30.30 3.30.30 Fixed
powertekpdus smart poms firmware < 3.30.30 3.30.30 Fixed
powertekpdus smart pos firmware < 3.30.30 3.30.30 Fixed

Affected products

ProductAffected versionsFixed in
powertekpdus basic pdu firmware < 3.30.30 3.30.30
powertekpdus pm pdu firmware < 3.30.30 3.30.30
powertekpdus piml pdu firmware < 3.30.30 3.30.30
powertekpdus smart pim firmware < 3.30.30 3.30.30
powertekpdus smart pos firmware < 3.30.30 3.30.30
powertekpdus smart pom firmware < 3.30.30 3.30.30
powertekpdus smart poms firmware < 3.30.30 3.30.30

References