CVE-2022-33175 Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_...
CriticalCVSS 9.8
EPSS 1.7%
- Published
- Updated
- Exploit status
- No public exploit known
Description
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| powertekpdus basic pdu firmware | < 3.30.30 | 3.30.30 |
| powertekpdus pm pdu firmware | < 3.30.30 | 3.30.30 |
| powertekpdus piml pdu firmware | < 3.30.30 | 3.30.30 |
| powertekpdus smart pim firmware | < 3.30.30 | 3.30.30 |
| powertekpdus smart pos firmware | < 3.30.30 | 3.30.30 |
| powertekpdus smart pom firmware | < 3.30.30 | 3.30.30 |
| powertekpdus smart poms firmware | < 3.30.30 | 3.30.30 |
References
- gynvael.coldwind.pl exploit third-party-advisory