Skip to content

CVE-2023-0052 SAUTER Controls Nova 200–220 Series Missing Authentication for Critical Function

HighCVSS 8.8 EPSS 0.74%
Published
Updated
Exploit status
No public exploit known

Description

SAUTER Controls Nova 200–220 Series with firmware version 3.3-006 and prior and BACnetstac version 4.2.1 and prior allows the execution of commands without credentials. As Telnet and file transfer protocol (FTP) are the only protocols available for device management, an unauthorized user could access the system and modify the device configuration, which could result in the unauthorized user executing unrestricted malicious commands.

Affected products

ProductAffected versionsFixed in
SAUTER Controls Nova 220 (EYK220F001) DDC with BACnet connection >= Firmware all versions, <= 3.3-006 No fix listed
SAUTER Controls Nova 220 (EYK220F001) DDC with BACnet connection >= BACnetstac all versions, <= 4.2.1 No fix listed
SAUTER Controls Nova 230 (EYK230F001) DDC with BACnet connection >= Firmware all versions, <= 3.3-006 No fix listed
SAUTER Controls Nova 230 (EYK230F001) DDC with BACnet connection >= BACnetstac all versions, <= 4.2.1 No fix listed
SAUTER Controls Nova 106 (EYK300F001) BACnet communication card >= Firmware all versions, <= 3.3-006 No fix listed
SAUTER Controls Nova 106 (EYK300F001) BACnet communication card >= BACnetstac all versions, <= 4.2.1 No fix listed
SAUTER Controls moduNet300 (EY-AM300F001, EY-AM300F002) >= Firmware all versions, <= 3.3-006 No fix listed
SAUTER Controls moduNet300 (EY-AM300F001, EY-AM300F002) >= BACnetstac all versions, <= 4.2.1 No fix listed
sauter-controls nova 220 eyk220f001 firmware <= 3.3-006 No fix listed
sauter-controls nova 230 eyk230f001 firmware <= 3.3-006 No fix listed
sauter-controls nova 106 eyk300f001 firmware <= 3.3-006 No fix listed
sauter-controls modunet300 ey-am300f001 firmware <= 3.3-006 No fix listed
sauter-controls modunet300 ey-am300f002 firmware <= 3.3-006 No fix listed

References