Skip to content

CVE-2023-26593 CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is....

HighCVSS 7.8 EPSS 0.14%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: no · technical impact: total

Description

CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege which CENTUM managed may be escalated. As a result, the control system may be operated with the escalated user privilege. To exploit this vulnerability, the following prerequisites must be met: (1)An attacker has obtained user credentials where the affected product is installed, (2)CENTUM Authentication Mode is used for user authentication when CENTUM VP is used. The affected products and versions are as follows: CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.00 and later, B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R7.04.51 and R8.01.01 and later

Upgrade path

9 packages: 4 fixed, 4 partially fixed.

PackageAffectedFixed inStatus
yokogawa bm9000 vp >= r6.01.01, <= r7.04.51; >= r8.01.01 after r7.04.51 Partially fixed
yokogawa centum vp >= r4.01.00, <= r4.03.00; >= r5.01.00, <= r5.04.20; >= r6.01.00 after r4.03.00, r5.04.20 Partially fixed
yokogawa centum vp entry class >= r4.01.00, <= r4.02.00; >= r5.01.00, <= r5.04.20; >= r6.01.00 after r4.02.00, r5.04.20 Partially fixed
yokogawa exaopc >= r1.01.00, <= r1.20.00; >= r2.01.00, <= r2.10.00; >= r3.01.00 after r1.20.00, r2.10.00 Partially fixed
yokogawa bm9000cs >= r5.04.01, <= r5.05.01 after r5.05.01 Fixed
yokogawa centum cs 1000 >= r2.01.00, <= r3.09.50 after r3.09.50 Fixed
yokogawa centum cs 3000 >= r2.01.00, <= r3.09.50 after r3.09.50 Fixed
yokogawa centum cs 3000 entry class >= r2.01.00, <= r3.09.50 after r3.09.50 Fixed
Yokogawa Electric Corporation CENTUM series = CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.0 No fix listed Versions listed

Affected products

ProductAffected versionsFixed in
Yokogawa Electric Corporation CENTUM series = CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.0 No fix listed
yokogawa bm9000 vp >= r6.01.01, <= r7.04.51 No fix listed
yokogawa bm9000 vp >= r8.01.01 No fix listed
yokogawa bm9000cs >= r5.04.01, <= r5.05.01 No fix listed
yokogawa centum cs 1000 >= r2.01.00, <= r3.09.50 No fix listed
yokogawa centum cs 3000 >= r2.01.00, <= r3.09.50 No fix listed
yokogawa centum cs 3000 entry class >= r2.01.00, <= r3.09.50 No fix listed
yokogawa centum vp >= r4.01.00, <= r4.03.00 No fix listed
yokogawa centum vp >= r5.01.00, <= r5.04.20 No fix listed
yokogawa centum vp >= r6.01.00 No fix listed
yokogawa centum vp entry class >= r4.01.00, <= r4.02.00 No fix listed
yokogawa centum vp entry class >= r5.01.00, <= r5.04.20 No fix listed
yokogawa centum vp entry class >= r6.01.00 No fix listed
yokogawa exaopc >= r1.01.00, <= r1.20.00 No fix listed
yokogawa exaopc >= r2.01.00, <= r2.10.00 No fix listed
yokogawa exaopc >= r3.01.00 No fix listed

References