CVE-2023-37551 CODESYS Files or Directories Accessible to External Parties in CmpApp
MediumCVSS 6.5
EPSS 0.50%
- Published
- Updated
- Exploit status
- No public exploit known
- CISA SSVC
- No known exploitation · automatable: no · technical impact: partial
Description
In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.
Upgrade path
32 packages: 32 fixed.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| CODESYS Control for BeagleBone SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for BeagleBone SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for emPC-A/iMX6 SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for emPC-A/iMX6 SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for IOT2000 SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for IOT2000 SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for Linux SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for Linux SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for PFC100 SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for PFC100 SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for PFC200 SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for PFC200 SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for PLCnext SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for PLCnext SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for Raspberry Pi SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for Raspberry Pi SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control for WAGO Touch Panels 600 SL | < V4.10.0.0 | V4.10.0.0 | Fixed |
| CODESYS Control for WAGO Touch Panels 600 SL | < 4.10.0.0 | 4.10.0.0 | Fixed |
| CODESYS Control RTE (for Beckhoff CX) SL | < V3.5.19.20 | V3.5.19.20 | Fixed |
| CODESYS Control RTE (SL) | < V3.5.19.20 | V3.5.19.20 | Fixed |
| CODESYS Control RTE (SL) | < 3.5.19.20 | 3.5.19.20 | Fixed |
| CODESYS control rte sl for beckhoff cx | < 3.5.19.20 | 3.5.19.20 | Fixed |
| CODESYS Control Runtime System Toolkit | < V3.5.19.20 | V3.5.19.20 | Fixed |
| CODESYS control runtime system toolkit | < 3.5.19.20 | 3.5.19.20 | Fixed |
| CODESYS Control Win (SL) | < V3.5.19.20 | V3.5.19.20 | Fixed |
| CODESYS Control Win (SL) | < 3.5.19.20 | 3.5.19.20 | Fixed |
| CODESYS development system | < 3.5.19.20 | 3.5.19.20 | Fixed |
| CODESYS Development System V3 | < V3.5.19.20 | V3.5.19.20 | Fixed |
| CODESYS hmi | < 3.5.19.20 | 3.5.19.20 | Fixed |
| CODESYS HMI (SL) | < V3.5.19.20 | V3.5.19.20 | Fixed |
… and 2 more packages.
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| CODESYS Control for BeagleBone SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for emPC-A/iMX6 SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for IOT2000 SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for Linux SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for PFC100 SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for PFC200 SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for PLCnext SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for Raspberry Pi SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control for WAGO Touch Panels 600 SL | < V4.10.0.0 | V4.10.0.0 |
| CODESYS Control RTE (for Beckhoff CX) SL | < V3.5.19.20 | V3.5.19.20 |
| CODESYS Control RTE (SL) | < V3.5.19.20 | V3.5.19.20 |
| CODESYS Control Runtime System Toolkit | < V3.5.19.20 | V3.5.19.20 |
| CODESYS Control Win (SL) | < V3.5.19.20 | V3.5.19.20 |
| CODESYS Development System V3 | < V3.5.19.20 | V3.5.19.20 |
| CODESYS HMI (SL) | < V3.5.19.20 | V3.5.19.20 |
| CODESYS Safety SIL2 Runtime Toolkit | < V3.5.19.20 | V3.5.19.20 |
| CODESYS Control for BeagleBone SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for emPC-A/iMX6 SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for IOT2000 SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for Linux SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for PFC100 SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for PFC200 SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for PLCnext SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for Raspberry Pi SL | < 4.10.0.0 | 4.10.0.0 |
| CODESYS Control for WAGO Touch Panels 600 SL | < 4.10.0.0 | 4.10.0.0 |
Show 7 more
| Product | Affected versions | Fixed in |
|---|---|---|
| CODESYS Control RTE (SL) | < 3.5.19.20 | 3.5.19.20 |
| CODESYS control rte sl for beckhoff cx | < 3.5.19.20 | 3.5.19.20 |
| CODESYS control runtime system toolkit | < 3.5.19.20 | 3.5.19.20 |
| CODESYS Control Win (SL) | < 3.5.19.20 | 3.5.19.20 |
| CODESYS development system | < 3.5.19.20 | 3.5.19.20 |
| CODESYS hmi | < 3.5.19.20 | 3.5.19.20 |
| CODESYS Safety SIL2 | < 3.5.19.20 | 3.5.19.20 |
References
- cert.vde.com third-party-advisory