CVE-2024-12169 A vulnerability exists in RTU500 IEC 60870-5-104 controlled station functionality and IEC 61850 functionality, that allows an attacker performing a specific attack sequence to restart the affected CMU...

HighCVSS 8.7 EPSS 0.73%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: no · technical impact: partial

Description

A vulnerability exists in RTU500 IEC 60870-5-104 controlled station functionality and IEC 61850 functionality, that allows an attacker performing a specific attack sequence to restart the affected CMU. This vulnerability only applies, if secure communication using IEC 62351-3 (TLS) is enabled.

Upgrade path

1 package: 1 fixed.

PackageAffectedFixed inStatus
Hitachi Energy RTU500 = 13.6.1; >= 13.4.1, <= 13.4.4; >= 13.5.1, <= 13.5.3; >= 13.7.1, <= 13.7.4 after 13.4.4, 13.5.3, 13.7.4 Fixed

Affected products

ProductAffected versionsFixed in
Hitachi Energy RTU500 >= 13.4.1, <= 13.4.4 No fix listed
Hitachi Energy RTU500 >= 13.5.1, <= 13.5.3 No fix listed
Hitachi Energy RTU500 = 13.6.1 No fix listed
Hitachi Energy RTU500 >= 13.7.1, <= 13.7.4 No fix listed