Skip to content

CVE-2025-24510 A vulnerability has been identified in MS/TP Point Pickup Module (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the...

HighCVSS 7.1 EPSS 0.27%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: no · technical impact: partial

Description

A vulnerability has been identified in MS/TP Point Pickup Module (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the same BACnet network to send a specially crafted MSTP message that results in a denial of service condition of the targeted device. A power cycle is required to restore the device's normal operation.

Upgrade path

1 package: 0 fixed, 1 with no fix yet.

PackageAffectedFixed inStatus
Siemens MS/TP Point Pickup Module All versions No fix listed No fix yet

Affected products

ProductAffected versionsFixed in
Siemens MS/TP Point Pickup Module All versions No fix listed

References