CVE-2025-3946 Incorrect response generation during FTEB protocol processing

HighCVSS 8.2 EPSS 0.55%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: no · technical impact: partial

Description

The Honeywell Experion PKS

and OneWireless WDM

contains a Deployment of Wrong Handler

vulnerability

in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to

Input Data Manipulation,

which could result in incorrect handling of packets leading to remote code execution.

Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1.

The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.

Upgrade path

10 packages: 10 fixed.

PackageAffectedFixed inStatus
honeywell C200E >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell C300 PCNT02 >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell C300 PCNT05 >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell C300PM >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell CN100 >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell FIM4 >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell FIM8 >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell HCA >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell UOC >= 520.1, <= 520.2 TCU9; >= 530, <= 530 TCU3 after 520.2 TCU9, 530 TCU3 Fixed
honeywell Wireless Device Manager >= 322.1, <= 322.4; >= 330.1, <= 330.3 after 322.4, 330.3 Fixed

Affected products

ProductAffected versionsFixed in
honeywell C300 PCNT02 >= 520.1, <= 520.2 TCU9 No fix listed
honeywell C300 PCNT02 >= 530, <= 530 TCU3 No fix listed
honeywell C300 PCNT05 >= 520.1, <= 520.2 TCU9 No fix listed
honeywell C300 PCNT05 >= 530, <= 530 TCU3 No fix listed
honeywell FIM4 >= 520.1, <= 520.2 TCU9 No fix listed
honeywell FIM4 >= 530, <= 530 TCU3 No fix listed
honeywell FIM8 >= 520.1, <= 520.2 TCU9 No fix listed
honeywell FIM8 >= 530, <= 530 TCU3 No fix listed
honeywell UOC >= 520.1, <= 520.2 TCU9 No fix listed
honeywell UOC >= 530, <= 530 TCU3 No fix listed
honeywell CN100 >= 520.1, <= 520.2 TCU9 No fix listed
honeywell CN100 >= 530, <= 530 TCU3 No fix listed
honeywell HCA >= 520.1, <= 520.2 TCU9 No fix listed
honeywell HCA >= 530, <= 530 TCU3 No fix listed
honeywell C300PM >= 520.1, <= 520.2 TCU9 No fix listed
honeywell C300PM >= 530, <= 530 TCU3 No fix listed
honeywell C200E >= 520.1, <= 520.2 TCU9 No fix listed
honeywell C200E >= 530, <= 530 TCU3 No fix listed
honeywell Wireless Device Manager >= 322.1, <= 322.4 No fix listed
honeywell Wireless Device Manager >= 330.1, <= 330.3 No fix listed

References