Skip to content

CVE-2025-40944 A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP...

HighCVSS 8.7 EPSS 0.44%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: yes · technical impact: partial

Description

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.

This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

Upgrade path

15 packages: 9 fixed, 6 with no fix yet.

PackageAffectedFixed inStatus
Siemens SIMATIC ET 200AL IM 157-1 PN All versions No fix listed No fix yet
Siemens SIMATIC ET 200MP IM 155-5 PN HF >= V4.2.0 No fix listed No fix yet
Siemens SIMATIC ET 200SP IM 155-6 MF HF All versions No fix listed No fix yet
Siemens SIMATIC PN/MF Coupler All versions No fix listed No fix yet
Siemens SIPLUS ET 200MP IM 155-5 PN HF >= V4.2.0 No fix listed No fix yet
Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL >= V4.2.0 No fix listed No fix yet
Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) < V1.3 V1.3 Fixed
Siemens SIMATIC ET 200SP IM 155-6 PN R1 < V6.0.1 V6.0.1 Fixed
Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF >= V4.2.0, < V4.2.5 V4.2.5 Fixed
Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF < V4.2.2 V4.2.2 Fixed
Siemens SIMATIC PN/PN Coupler < V6.0.0 V6.0.0 Fixed
Siemens SIPLUS ET 200SP IM 155-6 PN HF >= V4.2.0, < V4.2.5 V4.2.5 Fixed
Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL >= V4.2.0, < V4.2.5 V4.2.5 Fixed
Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL >= V4.2.0, < V4.2.5 V4.2.5 Fixed
Siemens SIPLUS NET PN/PN Coupler < V6.0.0 V6.0.0 Fixed

Affected products

ProductAffected versionsFixed in
Siemens SIMATIC ET 200AL IM 157-1 PN All versions No fix listed
Siemens SIMATIC ET 200MP IM 155-5 PN HF >= V4.2.0 No fix listed
Siemens SIMATIC ET 200SP IM 155-6 MF HF All versions No fix listed
Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) < V1.3 V1.3
Siemens SIMATIC ET 200SP IM 155-6 PN R1 < V6.0.1 V6.0.1
Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF >= V4.2.0, < V4.2.5 V4.2.5
Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF < V4.2.2 V4.2.2
Siemens SIMATIC PN/MF Coupler All versions No fix listed
Siemens SIMATIC PN/PN Coupler < V6.0.0 V6.0.0
Siemens SIPLUS ET 200MP IM 155-5 PN HF >= V4.2.0 No fix listed
Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL >= V4.2.0 No fix listed
Siemens SIPLUS ET 200SP IM 155-6 PN HF >= V4.2.0, < V4.2.5 V4.2.5
Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL >= V4.2.0, < V4.2.5 V4.2.5
Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL >= V4.2.0, < V4.2.5 V4.2.5
Siemens SIPLUS NET PN/PN Coupler < V6.0.0 V6.0.0

References