CVE-2025-40944 A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP...
- Published
- Updated
- Exploit status
- No public exploit known
- CISA SSVC
- No known exploitation · automatable: yes · technical impact: partial
Description
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.
This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
Upgrade path
15 packages: 9 fixed, 6 with no fix yet.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| Siemens SIMATIC ET 200AL IM 157-1 PN | All versions | No fix listed | No fix yet |
| Siemens SIMATIC ET 200MP IM 155-5 PN HF | >= V4.2.0 | No fix listed | No fix yet |
| Siemens SIMATIC ET 200SP IM 155-6 MF HF | All versions | No fix listed | No fix yet |
| Siemens SIMATIC PN/MF Coupler | All versions | No fix listed | No fix yet |
| Siemens SIPLUS ET 200MP IM 155-5 PN HF | >= V4.2.0 | No fix listed | No fix yet |
| Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL | >= V4.2.0 | No fix listed | No fix yet |
| Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) | < V1.3 | V1.3 | Fixed |
| Siemens SIMATIC ET 200SP IM 155-6 PN R1 | < V6.0.1 | V6.0.1 | Fixed |
| Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF | >= V4.2.0, < V4.2.5 | V4.2.5 | Fixed |
| Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF | < V4.2.2 | V4.2.2 | Fixed |
| Siemens SIMATIC PN/PN Coupler | < V6.0.0 | V6.0.0 | Fixed |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF | >= V4.2.0, < V4.2.5 | V4.2.5 | Fixed |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL | >= V4.2.0, < V4.2.5 | V4.2.5 | Fixed |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL | >= V4.2.0, < V4.2.5 | V4.2.5 | Fixed |
| Siemens SIPLUS NET PN/PN Coupler | < V6.0.0 | V6.0.0 | Fixed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Siemens SIMATIC ET 200AL IM 157-1 PN | All versions | No fix listed |
| Siemens SIMATIC ET 200MP IM 155-5 PN HF | >= V4.2.0 | No fix listed |
| Siemens SIMATIC ET 200SP IM 155-6 MF HF | All versions | No fix listed |
| Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) | < V1.3 | V1.3 |
| Siemens SIMATIC ET 200SP IM 155-6 PN R1 | < V6.0.1 | V6.0.1 |
| Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF | >= V4.2.0, < V4.2.5 | V4.2.5 |
| Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF | < V4.2.2 | V4.2.2 |
| Siemens SIMATIC PN/MF Coupler | All versions | No fix listed |
| Siemens SIMATIC PN/PN Coupler | < V6.0.0 | V6.0.0 |
| Siemens SIPLUS ET 200MP IM 155-5 PN HF | >= V4.2.0 | No fix listed |
| Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL | >= V4.2.0 | No fix listed |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF | >= V4.2.0, < V4.2.5 | V4.2.5 |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL | >= V4.2.0, < V4.2.5 | V4.2.5 |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL | >= V4.2.0, < V4.2.5 | V4.2.5 |
| Siemens SIPLUS NET PN/PN Coupler | < V6.0.0 | V6.0.0 |