CVE-2025-7693 Rockwell Automation Micro800 Vulnerability

CriticalCVSS 9.3 EPSS 0.40%
Published
Updated
Exploit status
No public exploit known

Description

A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.

Affected products

ProductAffected versionsFixed in
Rockwell Automation PLC - Micro850 L50E = V20.011 - V22.011 No fix listed