CVE-2025-9068 Rockwell Automation FactoryTalk® Linx Privilege Escalation Vulnerabilities
HighCVSS 8.5
EPSS 0.19%
- Published
- Updated
- Exploit status
- No public exploit known
- CISA SSVC
- No known exploitation · automatable: no · technical impact: partial
Description
A security issue exists within the Rockwell Automation Driver Package x64 Microsoft Installer File (MSI) repair functionality, installed with FTLinx. Authenticated attackers with valid Windows Users credentials can initiate a repair and hijack the resulting console window for vbpinstall.exe. This allows the launching of a command prompt running with SYSTEM-level privileges, allowing full access to all files, processes, and system resources.
Upgrade path
2 packages: 1 fixed.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| rockwellautomation factorytalk linx | < 6.50 | 6.50 | Fixed |
| Rockwell Automation FactoryTalk Linx | = 6.40 and prior | No fix listed | Versions listed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Rockwell Automation FactoryTalk Linx | = 6.40 and prior | No fix listed |
| rockwellautomation factorytalk linx | < 6.50 | 6.50 |
References
- www.rockwellautomation.com vendor-advisory