Skip to content

CVE-2026-127124 RPC session pool exhausted by unfinished fragmented requests

HighCVSS 7.1 EPSS 0.20%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: no · technical impact: partial

Description

P-Net before 1.0.4 keeps the RPC session that is allocated for a fragment of a request with an unknown activity UUID, without a timeout, when the rest of the request never arrives. A session that does not get an Application Relationship is also kept after the response. Repeated fragments or requests with different activity UUIDs exhaust the available sessions, one UDP packet per session. Once they are exhausted the device no longer answers a Connect request until it is restarted. An unauthenticated attacker with ADJACENT network access can use this to cause a denial of service.

Upgrade path

1 package: 1 fixed.

PackageAffectedFixed inStatus
RT-Labs AB P-Net < 1.0.4 1.0.4 Fixed

Affected products

ProductAffected versionsFixed in
RT-Labs AB P-Net < 1.0.4 1.0.4