Skip to content

CVE-2026-3611 Honeywell IQ4x BMS Controller Missing authentication for critical function

CriticalCVSS 10.0 EPSS 6.3%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: yes · technical impact: total

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Upgrade path

12 packages: 12 fixed.

PackageAffectedFixed inStatus
honeywell IQ3 >= v3.50_3.44, <= 4.36 (build 4.3.7.9) after 4.36 (build 4.3.7.9) Fixed
honeywell IQ412 >= v3.50_3.44, <= 4.36 (build 4.3.7.9) after 4.36 (build 4.3.7.9) Fixed
honeywell iq412 firmware < 3.30 3.30 Fixed
honeywell IQ41x >= v3.50_3.44, <= 4.36 (build 4.3.7.9) after 4.36 (build 4.3.7.9) Fixed
honeywell iq41x firmware < 3.30 3.30 Fixed
honeywell IQ422 >= v3.50_3.44, <= 4.36 (build 4.3.7.9) after 4.36 (build 4.3.7.9) Fixed
honeywell iq422 firmware < 3.30 3.30 Fixed
honeywell IQ4E >= v3.50_3.44, <= 4.36 (build 4.3.7.9) after 4.36 (build 4.3.7.9) Fixed
honeywell iq4e firmware < 3.30 3.30 Fixed
honeywell IQ4NC >= v3.50_3.44, <= 4.36 (build 4.3.7.9) after 4.36 (build 4.3.7.9) Fixed
honeywell iq4nc firmware < 3.30 3.30 Fixed
honeywell IQECO >= v3.50_3.44, <= 4.36 (build 4.3.7.9) after 4.36 (build 4.3.7.9) Fixed

Affected products

ProductAffected versionsFixed in
honeywell IQ4E >= v3.50_3.44, <= 4.36 (build 4.3.7.9) No fix listed
honeywell IQ412 >= v3.50_3.44, <= 4.36 (build 4.3.7.9) No fix listed
honeywell IQ422 >= v3.50_3.44, <= 4.36 (build 4.3.7.9) No fix listed
honeywell IQ4NC >= v3.50_3.44, <= 4.36 (build 4.3.7.9) No fix listed
honeywell IQ41x >= v3.50_3.44, <= 4.36 (build 4.3.7.9) No fix listed
honeywell IQ3 >= v3.50_3.44, <= 4.36 (build 4.3.7.9) No fix listed
honeywell IQECO >= v3.50_3.44, <= 4.36 (build 4.3.7.9) No fix listed
honeywell iq4e firmware < 3.30 3.30
honeywell iq412 firmware < 3.30 3.30
honeywell iq422 firmware < 3.30 3.30
honeywell iq4nc firmware < 3.30 3.30
honeywell iq41x firmware < 3.30 3.30

References