CVE-2026-39460 Red Lion Controls N-Tron 700 Series Insufficiently Protected Credentials
CriticalCVSS 9.3
EPSS 0.29%
- Published
- Updated
- Exploit status
- No public exploit known
- CISA SSVC
- No known exploitation · automatable: no · technical impact: total
Description
Usernames and passwords, including the default factory credentials, are stored in plaintext within the configuration file. With administrator rights, the configuration file can be viewed through the CLI or they can be exported from the device through a TFTP transfer from the web interface. A TFTP transfer can be initiated through SNMP which does not require authentication.
Upgrade path
1 package: 1 fixed.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| Red Lion Controls 700 Series | < Bootloader Versions 2.0.6.1; < Firmware Versions 3.11.0 | Bootloader Versions 2.0.6.1, Firmware Versions 3.11.0 | Fixed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Red Lion Controls 700 Series | < Firmware Versions 3.11.0 | Firmware Versions 3.11.0 |
| Red Lion Controls 700 Series | < Bootloader Versions 2.0.6.1 | Bootloader Versions 2.0.6.1 |