Skip to content

CVE-2026-59693 A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E0...

MediumCVSS 5.3 EPSS 0.24%
Published
Updated
Exploit status
No public exploit known
CISA SSVC
No known exploitation · automatable: no · technical impact: partial

Description

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.

Upgrade path

6 packages: 6 fixed.

PackageAffectedFixed inStatus
Siemens Desigo DXR2 < V01.21.233.16-7862 V01.21.233.16-7862 Fixed
Siemens Desigo PXC3 < V01.21.233.16-7862 V01.21.233.16-7862 Fixed
Siemens Desigo PXC4 < V02.21.194.36-2715 V02.21.194.36-2715 Fixed
Siemens Desigo PXC5.E003 < V02.21.194.36-2715 V02.21.194.36-2715 Fixed
Siemens Desigo PXC5.E24 < V02.21.194.36-2715 V02.21.194.36-2715 Fixed
Siemens Desigo PXC7 < V02.21.194.36-2715 V02.21.194.36-2715 Fixed

Affected products

ProductAffected versionsFixed in
Siemens Desigo DXR2 < V01.21.233.16-7862 V01.21.233.16-7862
Siemens Desigo PXC3 < V01.21.233.16-7862 V01.21.233.16-7862
Siemens Desigo PXC4 < V02.21.194.36-2715 V02.21.194.36-2715
Siemens Desigo PXC5.E003 < V02.21.194.36-2715 V02.21.194.36-2715
Siemens Desigo PXC5.E24 < V02.21.194.36-2715 V02.21.194.36-2715
Siemens Desigo PXC7 < V02.21.194.36-2715 V02.21.194.36-2715

References