CVE-2026-59693 A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E0...
- Published
- Updated
- Exploit status
- No public exploit known
- CISA SSVC
- No known exploitation · automatable: no · technical impact: partial
Description
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.
Upgrade path
6 packages: 6 fixed.
| Package | Affected | Fixed in | Status |
|---|---|---|---|
| Siemens Desigo DXR2 | < V01.21.233.16-7862 | V01.21.233.16-7862 | Fixed |
| Siemens Desigo PXC3 | < V01.21.233.16-7862 | V01.21.233.16-7862 | Fixed |
| Siemens Desigo PXC4 | < V02.21.194.36-2715 | V02.21.194.36-2715 | Fixed |
| Siemens Desigo PXC5.E003 | < V02.21.194.36-2715 | V02.21.194.36-2715 | Fixed |
| Siemens Desigo PXC5.E24 | < V02.21.194.36-2715 | V02.21.194.36-2715 | Fixed |
| Siemens Desigo PXC7 | < V02.21.194.36-2715 | V02.21.194.36-2715 | Fixed |
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Siemens Desigo DXR2 | < V01.21.233.16-7862 | V01.21.233.16-7862 |
| Siemens Desigo PXC3 | < V01.21.233.16-7862 | V01.21.233.16-7862 |
| Siemens Desigo PXC4 | < V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens Desigo PXC5.E003 | < V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens Desigo PXC5.E24 | < V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens Desigo PXC7 | < V02.21.194.36-2715 | V02.21.194.36-2715 |
References
- cert-portal.siemens.com
- ENISA EUVD EUVD-2026-56121 third-party-advisory