Skip to content

Vendor

LS Electric vulnerabilities

10 published CVES affecting LS Electric, from public sources (CVE.org, NVD, CISA KEV, FIRST EPSS, OSV).

Total
10
Critical
3
High
6
Medium
1
Low
0
Unscored
0
CISA KEV
0
Atom feed of LS Electric alerts

Products

Latest LS Electric CVEs

Newest publication first

  1. HighCVSS 8.4 EPSS 0.17%

    A Heap-based Buffer Overflow vulnerability exists within the parsing of PRJ files. The issues result from the lack of proper validation of user-supplied data, which can result in different memory corruption issues within the application, such as reading and writing past the end o...

  2. HighCVSS 8.4 EPSS 0.16%

    An Out-of-bounds Read vulnerability exists within the parsing of PRJ files. The issues result from the lack of proper validation of user-supplied data, which can result in different memory corruption issues within the application, such as reading and writing past the end of alloc...

  3. HighCVSS 8.4 EPSS 0.18%

    An out-of-bounds write vulnerability exists within the parsing of PRJ files. The issues result from the lack of proper validation of user-supplied data, which can result in different memory corruption issues within the application, such as reading and writing past the end of allo...

  4. CVE-2023-22807 CVE-2023-22807

    Published
    CriticalCVSS 9.8 EPSS 0.67%

    LS ELECTRIC XBC-DN32U with operating system version 01.80 does not properly control access to the PLC over its internal XGT protocol. An attacker could control and tamper with the PLC by sending the packets to the PLC over its XGT protocol.

  5. CVE-2023-22806 CVE-2023-22806

    Published
    HighCVSS 7.5 EPSS 0.37%

    LS ELECTRIC XBC-DN32U with operating system version 01.80 transmits sensitive information in cleartext when communicating over its XGT protocol. This could allow an attacker to gain sensitive information such as user credentials.

  6. CVE-2023-22805 CVE-2023-22805

    Published
    MediumCVSS 4.3 EPSS 0.72%

    LS ELECTRIC XBC-DN32U with operating system version 01.80 has improper access control to its read prohibition feature. This could allow a remote attacker to remotely set the feature to lock users out of reading data from the device.

  7. CVE-2023-22804 CVE-2023-22804

    Published
    CriticalCVSS 9.8 EPSS 0.71%

    LS ELECTRIC XBC-DN32U with operating system version 01.80 is missing authentication to create users on the PLC. This could allow an attacker to create and use an account with elevated privileges and take control of the device.

  8. CVE-2023-22803 CVE-2023-22803

    Published
    HighCVSS 7.5 EPSS 0.59%

    LS ELECTRIC XBC-DN32U with operating system version 01.80 is missing authentication to perform critical functions to the PLC. This could allow an attacker to change the PLC's mode arbitrarily.

  9. CVE-2023-0103 CVE-2023-0103

    Published
    HighCVSS 7.5 EPSS 0.66%

    If an attacker were to access memory locations of LS ELECTRIC XBC-DN32U with operating system version 01.80 that are outside of the communication buffer, the device stops operating. This could allow an attacker to cause a denial-of-service condition.

  10. CVE-2023-0102 CVE-2023-0102

    Published
    CriticalCVSS 9.1 EPSS 0.69%

    LS ELECTRIC XBC-DN32U with operating system version 01.80 is missing authentication for its deletion command. This could allow an attacker to delete arbitrary files.

Sources: CVE.org, NVD, CISA KEV, FIRST EPSS, OSV and public exploit-reference metadata. Product matching comes from the published CVE records. A proof-of-concept means public code exists; it is not evidence of exploitation.