Skip to content

Product

Hitachi Energy MicroSCADA X SYS600 vulnerabilities

14 published CVES affecting Hitachi Energy MicroSCADA X SYS600, from public sources (CVE.org, NVD, CISA KEV, FIRST EPSS, OSV).

Total
14
Critical
0
High
12
Medium
2
Low
0
Unscored
0
CISA KEV
0

Latest Hitachi Energy MicroSCADA X SYS600 CVEs

Newest publication first

  1. HighCVSS 8.8 EPSS 0.71%

    The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that are used in filesystem operations. If exploited the vulnerability allows the attacker to access or modify system files or other files that are critical to the a...

  2. HighCVSS 8.8 EPSS 0.67%

    A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent data. Note that to successfully exploit this vulnerability an attacker must have a valid credential.

  3. HighCVSS 7.5 EPSS 0.89%

    Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. Thi...

  4. MediumCVSS 4.4 EPSS 0.61%

    Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects...

  5. HighCVSS 7.5 EPSS 0.89%

    Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-o...

  6. HighCVSS 7.5 EPSS 0.92%

    Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future t...

  7. HighCVSS 8.8 EPSS 0.75%

    Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X SY...

Sources: CVE.org, NVD, CISA KEV, FIRST EPSS, OSV and public exploit-reference metadata. Product matching comes from the published CVE records. A proof-of-concept means public code exists; it is not evidence of exploitation.