Newest publication first

  1. HighCVSS 7.8 EPSS 0.20%

    CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege w...

  2. HighCVSS 8.8 EPSS 0.77%

    Violation of secure design principles exists in the communication of CAMS for HIS. Affected products and versions are CENTUM series where LHS4800 is installed (CENTUM CS 3000 and CENTUM CS 3000 Small R3.08.10 to R3.09.00), CENTUM series where CAMS function is used (CENTUM VP, CEN...

  3. HighCVSS 7.8 EPSS 0.26%

    The following Yokogawa Electric products contain insecure DLL loading issues. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.

  4. HighCVSS 8.8 EPSS 1.1%

    CAMS for HIS Server contained in the following Yokogawa Electric products improperly authenticate the receiving packets. The authentication may be bypassed via some crafted packets: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, f...

  5. HighCVSS 8.1 EPSS 0.85%

    CAMS for HIS Log Server contained in the following Yokogawa Electric products fails to properly neutralize log outputs: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, and E...

  6. HighCVSS 7.8 EPSS 0.27%

    'Root Service' service implemented in the following Yokogawa Electric products creates some named pipe with improper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to...

  7. HighCVSS 8.1 EPSS 0.85%

    CAMS for HIS Log Server contained in the following Yokogawa Electric products is vulnerable to uncontrolled resource consumption. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, from R6.01.00 to R6.08.00,...

  8. HighCVSS 7.8 EPSS 0.25%

    'Long-term Data Archive Package' service implemented in the following Yokogawa Electric products creates some named pipe with imporper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, an...

  9. HighCVSS 8.8 EPSS 1.1%

    Path traversal vulnerability exists in CAMS for HIS Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc vers...

  10. CriticalCVSS 9.8 EPSS 1.0%

    The following Yokogawa Electric products do not change the passwords of the internal Windows accounts from the initial configuration: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.0, Exaopc versions from R3.72.00 to R3.79.00.

  11. HighCVSS 8.1 EPSS 0.97%

    There is a path traversal vulnerability in CAMS for HIS Log Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, andfrom R6.01.00 to R6.08.00, Exao...

  12. CriticalCVSS 9.8 EPSS 4.2%

    Stack-based buffer overflow in Yokogawa CENTUM CS 1000 R3.08.70 and earlier, CENTUM CS 3000 R3.09.50 and earlier, CENTUM CS 3000 Entry R3.09.50 and earlier, CENTUM VP R5.04.20 and earlier, CENTUM VP Entry R5.04.20 and earlier, ProSafe-RS R3.02.10 and earlier, Exaopc R3.72.00 and...

  13. CriticalCVSS 9.8 EPSS 6.7%

    Stack-based buffer overflow in Yokogawa CENTUM CS 1000 R3.08.70 and earlier, CENTUM CS 3000 R3.09.50 and earlier, CENTUM CS 3000 Entry R3.09.50 and earlier, CENTUM VP R5.04.20 and earlier, CENTUM VP Entry R5.04.20 and earlier, ProSafe-RS R3.02.10 and earlier, Exaopc R3.72.00 and...

  14. CriticalCVSS 9.8 EPSS 4.2%

    Stack-based buffer overflow in Yokogawa CENTUM CS 1000 R3.08.70 and earlier, CENTUM CS 3000 R3.09.50 and earlier, CENTUM CS 3000 Entry R3.09.50 and earlier, CENTUM VP R5.04.20 and earlier, CENTUM VP Entry R5.04.20 and earlier, ProSafe-RS R3.02.10 and earlier, Exaopc R3.72.00 and...

  15. HighCVSS 7.8 EPSS 1.3%

    An unquoted search path vulnerability in Multiple Yokogawa products for Windows (Exaopc (R1.01.00 ? R3.77.00), Exaplog (R1.10.00 ? R3.40.00), Exaquantum (R1.10.00 ? R3.02.00 and R3.15.00), Exaquantum/Batch (R1.01.00 ? R2.50.40), Exasmoc (all revisions), Exarqe (all revisions), GA...

  16. HighCVSS 7.5 EPSS 3.3%

    Multiple Yokogawa products that contain Vnet/IP Open Communication Driver (CENTUM CS 3000(R3.05.00 - R3.09.50), CENTUM CS 3000 Entry Class(R3.05.00 - R3.09.50), CENTUM VP(R4.01.00 - R6.03.10), CENTUM VP Entry Class(R4.01.00 - R6.03.10), Exaopc(R3.10.00 - R3.75.00), PRM(R2.06.00 -...

  17. MediumCVSS 6.5 EPSS 0.29%

    A weakness in access controls in CENTUM CS 1000 all versions, CENTUM CS 3000 versions R3.09.50 and earlier, CENTUM CS 3000 Small versions R3.09.50 and earlier, CENTUM VP versions R6.03.10 and earlier, CENTUM VP Small versions R6.03.10 and earlier, CENTUM VP Basic versions R6.03.1...

  18. HighCVSS 7.5 EPSS 22.5% Framework module

    BKBCopyD.exe in the Batch Management Packages in Yokogawa CENTUM CS 3000 through R3.09.50 and CENTUM VP through R4.03.00 and R5.x through R5.04.00, and Exaopc through R3.72.10, does not require authentication, which allows remote attackers to read arbitrary files via a RETR opera...

  19. HighCVSS 8.3 EPSS 62.3% Framework module Public exploit

    Stack-based buffer overflow in BKFSim_vhfd.exe in Yokogawa CENTUM CS 1000, CENTUM CS 3000 R3.09.50 and earlier, CENTUM VP R5.03.20 and earlier, Exaopc R3.72.00 and earlier, B/M9000CS R5.05.01 and earlier, and B/M9000 VP R7.03.01 and earlier, when FCS/Test Function is enabled, all...

  20. HighCVSS 8.3 EPSS 56.7% Framework module Public exploit

    Stack-based buffer overflow in BKESimmgr.exe in the Expanded Test Functions package in Yokogawa CENTUM CS 1000, CENTUM CS 3000 Entry Class R3.09.50 and earlier, CENTUM VP R5.03.00 and earlier, CENTUM VP Entry Class R5.03.00 and earlier, Exaopc R3.71.02 and earlier, B/M9000CS R5.0...

Sources: CVE.org, NVD, CISA KEV, FIRST EPSS, OSV and public exploit-reference metadata. Product matching comes from the published CVE records. A proof-of-concept means public code exists; it is not evidence of exploitation.